Technical Data Earth Leakage TM-8000s
Measurement True RMS Ampere
Current Setting (A) l∆n> 0.05 - 0.1 - 0.3 - 0.5 - 0.8 - 1.0 - 1.5 - 2.0 - 2.5 - 3.0
Trip Time Setting t> 0.05 - 10.0 (0.1 sec step)
High Set l∆n> 5 - 20 Ampere ( 1 Amp. step)
t>> Fixed at 50ms
Tripping Contact SPDT 5A/40V AC K1 : Latching trip
K2 : Programmable
Power Supply 240V AC, 50 Hz (Optional: 110VAC 50 Hz)
Z.C.T. 200 / 1.5mA
Weight approx. 500g
Ambient Temperature 0°C to +70°C
Standard IEC 1000-4-4, IEC 1000-4-5, IEC 255-5
Z.C.T. ZPC 35 ZPC 50 ZPC 100
Frequency 50 / 60 Hz
Current Ratio 200 / 1.5 mA
Insulation 600V / 50 Hz 1 min.
Sec. Burden 10 Va
Weight ~320g ~720g ~1.4 kg
Hole Diameter 35 mm 50 mm 100 mm
Dimension (A x B x C) 82 x 103 x 26 125 x 112 x 35 183 x 153 x 35
Z.C.T. dimension is measured in mm.