Technical
Data |
TM-8200s |
TM - 8300s |
Measurement |
True RMS |
Current Rating
(lE) |
5A |
Current Setting
Range (lE>) |
2% - 50% |
Time Setting
Range (tlE>) |
0.05 - 10.0 sec (0.1 sec step) |
0.05 - 10.00 sec (0.01 time
multiplier) |
High Set Range
(lE>>) |
10%
- 500% |
2 -
990% or OFF |
High Set Time
Setting Range (tlE>>) |
Fixed at 50 ms |
0.05 - 10.0 (0.1 sec step) |
IDMT
Graph |
Normal Inverse : 3.0 / 10 Normal Inverse : 1.3
/ 10 Very Inverse Extremely Inverse
(standard) Extremely Inverse (0.64) Long Time
Inverse |
Relay Operation
Level |
ln
/ ls >= 1.0 |
ln
/ ls >= 1.0 |
Display Range
(ln) |
0.0% ~ 500% |
0.0% ~ 990% >990% display
'out' |
Min
Sensitivity |
approx. 0.5% |
Tripping
Contact |
SPDT 5A/240V AC |
K1 : Latching |
K2 :
Programmable | |
Power
Supply |
240V AC, 50 Hz (Optional: 110VAC 50
Hz) |
240V AC, 50/60 Hz (Optional: 110VAC 50/60
Hz) |
C.T. Input /
Burden |
.../5A / 1VA |
Weight |
approx. 600g |
Ambient
Temperature |
0°C to +70°C |
Standard |
IEC 1000-4-4, IEC 1000-4-5, IEC
255-5 |